Bus Bar Design Considerations
Busbar Design Considerations
TABLE 2. QUICK BUSBAR SIZE SELECTOR
| Required Ampacity* | Busbar Dimension, Inches** | ||
|---|---|---|---|
| 30 °C Rise | 50 °C Rise | 65 °C Rise | |
| 100-149 | 1/16 x 1/2 1/16 x 3/4 |
1/16 x 1/2 | |
| 150-199 | 16 x 1 1/8 x 1/2 3/16 x 1/2 |
1/16 x 3/4 | 1/16 x 1/2 |
| 200-249 | 1/8 x 3/4 1/4 x 1/2 |
1/8 x 1/2 | 1/16 x 3/4 1/8 x 1/2 |
| 250-299 | 1/16 x 1 1/2 1/8 x 1 3/16 x 3/4 |
1/16 x 1 1/8 x 3/4 3/16 x 1/2 |
1/16 x 1 |
| 300-349 | 1/16 x 2 3/16 x 1 1/4 x 3/4 |
1/4 x 1/2 | 1/8 x 3/4 3/16 x 1/2 |
| 350-399 | 1/8 x 1 1/2 | 1/8 x 1 3/16 x 3/4 |
1/4 x 1/2 |
| 400-449 | 1/4 x 1 3/8 x 3/4 |
1/4 x 3/4 | 1/16 x 1 1/2 1/8 x 1 3/16 x 3/4 |
| 450-499 | 1/8 x 2 3/16 x 1 1/2 |
1/16 x 2 3/16 x 1 |
1/4 x 3/4 |
| 500-599 | 1/4 x 1 1/2 3/8 x 1 |
1/8 x 1 1/2 1/4 x 1 3/8 x 3/4 |
1/16 x 2 1/8 x 1 1/2 3/16 x 1 |
| 600-699 | 1/8 x 2 1/2 3/16 x 2 1/2 x 1 |
1/8 x 2 3/16 x 1 1/2 3/8 x 1 |
1/4 x 1 3/8 x 3/4 |
| 700-799 | 1/8 x 3 3/16 x 2 1/2 1/4 x 2 3/8 1 1/2 |
1/4 x 1 1/2 | 1/8 x 2 3/16 x 1 1/2 3/8 x 1 |
| 800-899 | 1/8 x 3 1/2 3/16 x 3 1/4 x 2 1/2 3/8 x 2 |
1/8 x 2 1/2 3/16 x 2 1/2 x 1 |
1/4 x 1 1/2 |
| 900-999 | 3/16 x 3 1/2 1/4 x 3 |
3/16 x 2 1/2 1/4 x 2 3/8 x 1 1/2 |
3/16 x 2 1/2 x1 |
| 1000-1249 | 3/16 x 4 1/4 x 3 1/2 3/8 x 2 1/2 3/8 x 3 1/2 x 2 1/2 x 2 1/2 |
1/8 x 4 3/16 x 3 1/4 x 2 1/2 3/8 x 2 |
1/8 x 3 3/16 x 2 1/2 1/4 x 2 3/8 x 1 1/2 |
| 1250-14999 | 1/4 x 4 3/8 x 3 1/2 1/2 x 3 |
3/16 x 3 1/2 3/16 x 4 1/4 x 3 3/8 x 2 1/2 1/2 x 2 |
1/8 x 4 3/16 x 3 1/4 2 1/2 3/8 x 2 |
| 1500-1749 | 1/4 x 5 3/8 x 4 1/2 x 3 1/2 1/2 x 4 |
1/4 x 3 1/2 1/4 x 4 3/8 x 3 1/2 x 2 1/2 |
3/16 x 3 1/2 3/16 x 4 1/4 x 3 3/8 x 2 1/2 1/2 x 2 |
| 1750-1999 | 1/4 x 6 3/8 x 5 |
3/8 x 3 1/2 1/2 x 3 |
1/4 x 3 1/2 1/4 x 4 3/8 x 3 1/2 x 2 1/2 |
| 2000-2499 | 1/4 x 8 3/8 x 6 1/2 x 5 1/2 x 6 |
1/4 x 6 3/8 x 5 1/2 x 4 |
1/4 x 5 3/8 x 4 1/2 x 3 1/2 |
| 2500-2999 | 1/4 x 10 3/8 x 8 |
3/8 x 6 1/2 x 5 |
1/4 x 6 3/8 x 5 1/2 x 4 |
* For 60 Hz current.
** Table gives busbar cross section which will probably be large enough for Ampacities within each range. Knowing required ampacity, determine possible busbar dimensions from the table. Then check Table 1 to verify that size selected has the necessary ampacity. Example: Assume that required ampacity is 185 amps at 30 °C rise. Table 2 indicates that 1/16 x 1 in. size would probably be adequate. This is confirmed by Table 1 which lists the ampacity of 1/6 x 1 in. busbar as 187 amps.